1b. Lift Station 3 Modifications
CITY OF
CHANHASSEN
7700 Market Boulevard
PO Box 147
Chanhassen, MN 55317
Administration
Phone: 952.227.1100
Fax: 952.227.1110
Building Inspections
Phone: 952.227.1180
Fax: 952.227.1190
Engineering
Phone: 952.227.1160
Fax: 952.227.1170
Finance
Phone: 952.227.1140
Fax: 952.227.1110
Park & Recreation
Phone: 952.227.1120
Fax: 952.227.1110
Recreation Center
2310 Coulter Boulevard
Phone: 952.227.1400
Fax: 952.227.1404
Planning &
Natural Resources
Phone: 952.227.1130
Fax: 952.227.1110
Public Works
1591 Park Road
Phone: 952.227.1300
Fax: 952.227.1310
Senior Center
Phone: 952.227.1125
Fax: 952.227.1110
Web Site
www.cLchanhassen.mn.us
1.1:>
f'".,,t,,~,
MEMORANDUM
o.
?(
TO:
Paul Oehme, City EngineerlDir. of Public Works
FROM:
Joseph Shamla, Project Engineer
fJ~
DATE:
August 27, 2007
SUBJ:
Lift Station No.3 Modifications Project No. 07-03:
Approve Construction Bid, Award Construction Contract and
Approve Electrical Control Panel Quote.
REQUEST (Simple Majority Vote Required)
Staff requests the City Council approve a construction contract in the amount of
$214,503.00 to Parrott Contracting, Inc. and a quote for an electrical panel to Quality
Flow in the amount of $27,954.12.
BACKGROUND
On February 12, 2007, Council authorized the preparation of plans and specifications
for the Lift Station No.3 Modifications Project.
On July 23, 2007, the City Council approved plans and specifications and
authorized advertisement for bid.
Lift Station No.3 is located on the north side of Trunk Highway 7 just west of
Church Road. The station was built in 1972 and is the main collection point for
wastewater in the western portion of the city. Four smaller lift stations flow into Lift
Station No.3. The flows from Lift Station No.3 go directly into the Metropolitan
Council sewer system. The service area of Lift Station No.3 has grown substantially
in recent years including a large development just to the west of the station. The size
of the lift station wet well and pumps are not large enough anymore to handle the
flows effectively.
The new SCADA system installed in 2005 identified problems with Lift Station
No.3. A review of the pump run times and hourly cycles for this station revealed the
pumps are cycling at an exorbitant rate. This cycling is indicative of insufficient wet
well capacity for proper operation of the pumps. The increased cycles of the pumps
can be attributed to additional flow from new developments in the area. As new
developments are completed, the cycling has increased. Also, the lift station appears
to have groundwater infiltration problems.
PROJECT SUMMARY
The scope of the Lift Station No.3 project is as follows:
The City of Chanhassen · A growing community with clean lakes, quality schools, a Charming downtown, thriving businesses, winding trails, and beautiful parks. A great place to live, work, and play.
Lift Station No.3 Modifications
July 23, 2007
Page 2
· A new wet well will be provided with sufficient capacity for ultimate build-out of
the lift station area. Utility crews should have adequate time to service the lift
station in the event a major problem occurs.
· New pumps are included in the scope of work and are sized for ultimate flow of
the new head (pumping) conditions of the wet well.
· The power supply in this area constantly has power supply disruptions and an
alternate source of power should be planned for at the station. Due to the amount
of flow to the station and the distance the lift station is from the Public Works
building, the lift station control panel will be designed with the capabilities of a
secondary power supply (standby generator). A backup generator is proposed to
be purchased in 2008 and is not included in this construction contract.
Bids
Bids for the project were opened on Thursday, August 16,2007, at 2:00 p.m. Two
total bids were submitted. The bids received are as follows:
Base Bid
Parrott Contracting Inc. $214,503.00
Magney Construction Inc. $309,155.00
The engineer's estimate for the project was $313,509.00.
Parrott Contracting, Inc. has completed several utility projects for the City of
Chanhassen. Their past work has been acceptable.
Control Panel Quote
A new control panel will need to be purchased for the station. In order to save on
contractor mark-ups, a separate quote was received for the control panel. The City
has standardized the lift station panels for system continuity and ease of repair.
The City has received the following quotes for the new electrical control panel:
Siemens Water Technology:
Quality How:
$30,863.70
$27,954.12
FUNDING
This project was programmed in the 2007 CIP Project SS-O 17. The total construction
cost of this project is $242,457.12. Funding for the project is proposed from the
sanitary sewer utility fund.
G:\ENG\PUBLla_2007 Projects\07-03 Lift Station No. 3\08-27-07 Award Contract.doc
Lift Station No.3 Modifications
July 23, 2007
Page 3
RECOMMENDA TION
Staff recommends that the City Council adopt the following motion:
"The Chanhassen City Council awards a construction contract for the Lift Station
No.3 Modifications Project to Parrott Contracting, Inc. in the amount of
$214,503.00 and approves an electrical control panel quote to Quality Flow in the
amount of $27,954.12."
Attachment: 1. CIP Page
2. Service Area Map
3. Location Map
G:\ENG\PUBLIO_2007 Projects\07-03 Lift Station No. 3\08-27-07 Award Contract.doc
Description I
- The sanitary lift station rehabilitation program is designed to minimize sewer backups and emergency calls due to failed lift station equipment The
City currently maintains 30 lift stations. Many of these lift stations are high service pumps and need frequent servicing. The program will service
or replace pumps, pipe gallery, and electrical components as needed. Lift Station #3 is recommended for improvements in 2007. Lift Station #3
located on the north side of Highway 7 takes all the flow from the properties on the west side of Lake Minnewashta and properties on the north side
of Highway 7. The wet well capacity has become undersized for flows. The electrical panel has become unreliable and needs to be replaced. The
electrical power in this area is unreliable, so a permanent backup generator is recommended.
r
I
I
Capital Improvement Program 2007 thru 2011
City of Chanhassen, MN
Project # SS-017
Project Name Sanitary Lift Station Rehabilitation Program
I
I
Account # 1 701-0000-4751
Account #2
Account # 3
,
II
Contact Unassigned
Department Sanitary Sewer Improvements
Type Improvement
Useful Life Unassigned
Category Utilities
Priority nta
Total Project Cost $475,000
II
Justification
I
Reduce emergency calls and potential sewer backups.
,
'i
~
I
2007 2008
265,000 / 50,000
,Total 265,000/ 50,000
~
2009
50,000
50,000
2010
55,000
55,000
Expenditures
Maintenance
III
II
II
Funding Sources
Sewer Utility Fund
2007
265,000
265,000
2008
50,000
50,000
2009
50,000
50,000
2010
55,000
55,000
Total
2011
55,000
55,000
Total
475,000
475,000
2011
55,000
55,000
Total
475,000
475,000
II
II
Operational Impact/Other
I
II
II
~
.
~
89
Lift Station 3 Service Area
. Lift Stations
_ Sewer Main
L-':::'] Service Area for Lift Station 3
--\
Lake Virginia
\
r
~I
Lake
Minnewashta
;/70 ~
'Q <)CI';~
f - 01,'. :~~.~
I\~--~-- ~
!:j'--lfieq[---'-,
!r.-.~ ,) I
~->"7?1
ff~::?i '''~
r- 0r~: "
~---"'::"/'L
---~~ ,..~~
~ ,.~Ij -'<::::"~:""":::::':''"':''::'''-:::::''......
-.----
+
r>-
G:\ENGVo/eenIEngPmjeclsIPau/ILS3
Jallumy 30. 2007
~f'"
,f .f
').: -;',-r"
t
....~(;
"!'
_J
5-.11 EXM' ..... E--- iU S.--
"'--" II! : . i -IEtI' ......,
Quotation
Siemens Water Technologies Corp.
1239 WILLOW LAI<E BLVD
VADNAIS HEIGHTS, MN 55110
Phone: 651.766.2700
Fax: 651.766.2701
Page 1 of 4
To:
City of Chanhassen
Kelley Janes
Quotation Date:
Bid Date / Time:
Estimated by:
Phone Number:
Salesperson: MS
Customer Reference: Lift Station No.3
.
7/11/07
WFA
Attn:
Phone:
Fax:
E-Mail:
Project: Channhassen, MN
Quotation Number:
070711WFA1QFPM
Revision History:
0- Initial Issue
Siemens Water Technologies is pleased to provide a quotation in accordance with a letter and PDF file
(Engineer's letter) received by email on 7/6/07.
Our itemized scope of supply is listed below. Siemens Water Technologies will not provide any items that
are not specifically listed.
Item Qtv. Description
A. . 1 Custom Powerpack Express in a free standing double door NEMA 3R enclosure
fabricated of galvanized steel and painted Forest Green. The enclosure will have a 3-
point padlockablelatch, skirted floor stand and inner doors. The equipment will control
the operation of two 30 HP submersible pumps, in a pump-down mode, in accordance
with the level of the wet well as monitored by a submersible level transducer and backup
float switches.
To Include:
Incoming Service Information
Volts: 480 Phase: 3 Wire: 4 Hertz: 60
Pump Motor'lnfo'rmation
HP: 30 FLA: approx 40 # of Pumps: 2 Pu'mp Type: Submersible
GENERAL CONTROL PANEL REQUIREMENTS
1 UL 913
1 SERVICE ENTRANCE LABEL
CONTROL PANEL ENCLOSURE
1 LOW PROFILE
1 NEMA 3R
ENCLOSURE MATERIAL
1 STEEL
ENCLOSURE MODIFICATIONS
1 DEAD FRONT
1 LATCH (3-PT)
1 LEGS (12")
1 SKIRTS
1 PAINTED FOREST GREEN
1 CONDENSATION HEATER /THERMOSTAT
'SIEME,NS
Quotation
Siemens Water Technologies Corp.
1239 WILLOW LAI<E BLVD
VADNAIS HEIGHTS. MN 55110
Phone: 651.766.2700
Fax: 651.766.2701
Page 2 of 4
Item Qtv. Description
CIRCUIT BREAKERS
1 . MAIN (200A thermal-mag w/auxiliary contact)
2 MOTOR
3 Q FRAME (CONTROL, ENGINE HEATER, BATTERY CHARGER)
1 RECEPTACLE (GFI)
LIGHTNING I SURGE ARRESTORS
2 PHASE MONITOR
1 LIGHTNING ARRESTOR
MOTOR STARTERS
2 SOLID STATE (Reduced Voltage Soft Start) (Motortronics, Model VMX)
MAIN CONTROLLER
1 D152 O-XX FT.
BACK-UP CONTROLLER
1CB1T
NEMA 4X INDICATOR LIGHT TYPE
2 120 VAC TRANSFORMER TYPE PRESS TO TEST LIGHTS
INDICATOR LIGHT FUNCTION
2 PUMP RUN
NEMA 4X SELECTOR SWITCHES
2 3 POSITION SELECTOR SWITCH
SELECTOR SWITCH FUNCTION
2 PUMP HAND-OFF-AUTO
_ NEMA 4X PUSHBUTTONS
1 MOMENTARY
PUSHBUTTON FUNCTION
1 ALARM SILENCE
RUNNING TIME METERS
2 PUMP RUN
1 SIMULTANEOUS PUMP RUN
OVERTEMP I SEAL FAIL
2 MINI CAS (MOUNT & WIRE MINI-CAS II ON INNER DOOR)
ALARM DIALERS
1 ALARM HORN
1 ALARM LIGHT
MAIN TRANSDUCER
1 A1000GSet-StlBMERSIBl:E-l:EVEL TRANSDUCER wI 60 ft. cable
1 A1000 CABLE SUSPENSION KIT wI 40 ft. cable
1 IS1-3INTRINSIC SAFETY BARRIER 1-5 VDC
BACK.UP TRANSDUCER
3 LS FLOAT (SUSPENDED TYPE)
1 IS6 INTRINSIC SAFETY BARRIER
MISCELLANEOUS
1 300 AMP - AUTOMATIC TRANSFER SWITCH (ASCO SERIES 300)
1 TRANSFORMER 480/120 VOLT 3 KVA W/PRI & SEC FUSING
Total Sell Price for Item A is $28,980.00 net; excluding all taxes and commissions
~,S%
--P3 CI ;3&3.+0 .
Exclusions: r
Unless specificallv referenced above, Siemens Water Technologies excludes:
SIEMEN'S
Quotation
Siemens Water Technologies Corp.
1239 WILLOW LAI<E BLVD
VADNAIS HEIGHTS. MN 55110
Phone: 651.766.2700
Fax: 651.766.2701
Page 3 of4
. All taxes, fees, permits, lien waivers, bonds and licenses.
. Startup, modifications and training trips and services.
. Onsite installation supervision.
. ISA loop drawings or P&IDs.
. Pricing for items having a quantity of more than 1 cannot be assumed to be equally divisible into
the total item price. If a quantity less than quoted is required please consult Siemens Water
Technologies for pricing verification or a new quotation.
. Receipt, storage, setting in place, installing or terminating any equipment or instrument.
. The supply of any mechanical appurtenances for panels or instruments. This includes, but is not
limited to power company transformers/metering, pumps, motors, pull boxes, junction boxes,
piping, tubing, valves, lighting panels, transformers, anchors, support stands, ground cables or
rods, stilling wells, etc.
. The supply of interconnecting materials external to enclosures, Le. wiring, cable, conduit, pressure
taps, tubing, telemetry or phone lines, or special cables.
. The supply of or installation of separate mounting brackets, bases, stands, pushbutton stations,
power fuses, pilot control switches, disconnects, manual starters or disconnect panels unless
specifically listed in our scope of supply.
. Any demolition, removal, transfer or disposal.
. Concrete work of any type.
. Installation and final termination of all wires or cables.
. Communication cable / telephone line coordination or connection.
. Jobsite progress or preconstruction meeting attendance.
. Any specialty electrical testing, including but not limited to insulation, resistance, grounding.
. Any specialty tools used for construction, testing or startup of equipment.
Proposed Delivery Schedule:
Drawings 2 to 3 weeks after acceptance of order, delivery 6 to 8 weeks after approval.
Siemens Water Technologies' commitment to deliver in accordance within the contract schedule is
contingent upon a prompt receipt of order, prompt negotiations of terms and conditions and a prompt
submittal review/approval process. Our timeline for delivery schedules will begin once terms and conditions
are negotiated and agreed upon by buyer and seller.
Deliverv and StoraQe:
Freight pre-pay and add. F.O.B. Shipping Point: 9.!.f~I~'I.~ing_~nd storage at site is the responsibility of
others.
Terms:
Quotation is valid for 90 days. Based on Siemens Water Technologies General Terms and Conditions of
sale, copy attached. An invoice for the total purchase price will be issued upon shipment.
Invoice payment terms net 30 days (based upon credit approval).
Thank you for this opportunity to be of service to you. If you have any questions, please don't hesitate to call.
Sincerely,
~~
Application Engineer
S,IEME,NS
Quotation
Siemens Water Technologies Corp.
1239 WILLOW LAKE BLVD
VADNAIS HEIGHTS, MN 55110
Phone: 651.766.2700
Fax: 651.766.2701
Page 4 of 4
SIEMENS WATER TECHNOLOGIES CORP.
CONTROL SYSTEMS PROOUCTS & SERVICES
EXHIBIT "An STANDARD TERMS OF THE SALE OF EauIPMENT
1. Applicable Terms. These terms govern the purchase and sale of the equipment and related services, If any (collectively, "Equipment"), referred to In
Seller's purchase order, quotation, proposal or acknowledgment, as the case may be ("Seller's Documentation"). Whether these terms are Included in an
offer or an acceptance by Seller, such offer or acceptance Is conditioned on Buyer's assent to these terms. Seller rejects all additional or different terms in
any of Buyer's forms or documents.
2. Pavment. Buyer shall pay Seller the full purchase price as set forth In Seller's Documentation. Unless Seller's Documentation provides otherwise,
freight, storage, Insurance and all taxes, duties or other governmental charges relating to the Equipment shall be paid by Buyer. If Seller Is required to pay
any such charges, Buyer shall immediately reimburse Seller. All payments are due within 30 days efter receipt of Invoice. Buyer shall be charged the lower
of 1 %% interest per month or the maximum legal rate on all amounts not received by the due date and shall pay all of Seller's reasonable costs (Including
attorneys' fees) of collecting amounts due but unpaid. All orders are subject to credit approval.
3. Deliverv. Delivery of the Equipment shall be In material compliance with the schedule In Seller's Documentation. Unless Seller's Documentation
provides otherwise, Delivery terms are F.O.B. Seller's facility. The risk of loss shall pass to the Buyer upon delivery of the equipment to the carrier.
4. Ownership of Materials. All devices, designs (Including drawings, plans and specifications), estimates, prices, notes, electronic data and other
documents or Information prepared or disclosed by Seller, and all related Intellectual property rights, shall remain Seller's property. Seller grants Buyer a
non-exclusive, non-transferable license to use any such material solely for Buyer's use of the Equipment. Buyer shall not disclose any such material to third
parties without Seller's prior written consent.
5. Chances. Seller shall not Implement any changes In the scope of work described In Seller's Documentation unless Buyer and Seller agree in writing
to the details of the change and any resulting price, schedule or other contractual modifications. This Includes any changes necessitated by a change in
applicable law occurring after the effective date of any contract Including these terms.
6. Warrantv. Subject to the following sentence, Seller warrants to Buyer that the Equipment shall materially conform to the description in Seller's
Documentation and shall be free from defects in material and workmanship. The foregoing warranty shall not apply to any Equipment that Is specified or
otherwise demanded by Buyer and Is not manufactured or selected by Seller, as to which (I) Seller hereby assigns to Buyer, to the extent assignable, any
warranties made to Seller and (Ii) Seller shall have no other liability to Buyer under warranty, tort or any other legal theory. If Buyer gives Seller prompt
wrillen notice of breach of this warranty within 18 months from delivery or 1 year from acceptance, whichever occurs first (the "Warranty Period"), Seller
shall, at its sole option and as Buyer's sole remedy, repair or replace the subject parts or refund the purchase price therefore. Provided however, all
transportation charges for the return of and the cost of labor for removal of the defective Equipment or, the re-Installation of the repaired or replacement
Equipment shall be paid by the Buyer. Replaced Equipment shall become the property of the Seller. In the case of a material defect in paid services,
provided under contract, Seller's sole obligation shall be to re-perform the services to meet the requirements. If Seller determines that any claimed breach Is
not, In fact, covered by this warranty, Buyer shall pay Seller Its then customary charges for any repair or replacement made by Seller. Seller's warranty Is
conditioned on Buyer's (a) operating within speCifications and maintaining the Equipment In accordance with Seller's instructions, (b) not making any
unauthorized repairs, alterations or, additions and (c) not being In default of any payment obligation to Seller. Seller's warranty does not cover damage
caused by chemical action, corrosion, dust or dirt, wear and tear under normal operating conditions, burnout, exposure to environmental, operational,
electrical, surges or, lightning conditions exceeding specifications, accident or catastrophe, misuse, abuse, improper handling or storage or, Improper
installation (unless installed by Seller). THE WARRANTIES SET FORTH IN THIS SECTION ARE SELLER'S SOLE AND EXCLUSIVE WARRANTIES AND
ARE SUBJECT TO SECTION 10 BELOW. SELLER MAKES NO OTHER WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING WITHOUT
LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR PURPOSE.
7. Indemnltv. Seller shall Indemnify, defend and hold Buyer harmless from any claim, cause of action or liability Incurred by Buyer as a result of third
party claims for personal injury, death or damage to tangible property, to the extent caused by Seller's negligence. Seller shall have the sole authority to
direct the defense of and settle any indemnified claim. Seller's Indemnification 15 conditioned on Buyer (a) promptly, within the Warranty Period, notifying
.___S_eJJJ;lL!!l.Wliting-91JlDy_cl.alm, and (b) provjdlngr.e~_g!lap~<;9QRer.aljon In the defense of an~ claim.
8. Force Ma1eure. Neither Seller nor Buyer shall have any liability for any breach (except for breach of payment obligations) caused by extreme weather
or other act of God, strike or other labor shortage or disturbance, fire, accident, war or civil disturbance, delay of carriers, failure of normal sources of
supply, act of'government or any other cause beyond such party's reasonable control.
g. Cancellation. If Buyer cancels or suspends its order for any reason other than Seller's breach, Buyer shall promptly pay Seller for work performed
prior to cancellation or suspension and any other direct costs Incurred by Seller as a result of such cancellation or suspension.
10. LIMITATION OF LIABILITY. NOTWITHSTANDING ANYTHING ELSE TO THE CONTRARY, SELLER SHALL NOT BE LIABLE FOR ANY
CONSEQUENTIAL, INCIDENTAL, SPECIAL, PUNITIVE OR OTHER INDIRECT DAMAGES, AND SELLER'S TOTAL LIABILITY ARISING AT ANY TIME
FROM THE SALE OR USE OF THE EQUIPMENT SHALL NOT EXCEED THE PURCHASE PRICE PAID FOR THE EQUIPMENT. THESE LIMITATIONS
APPLY WHETHER THE LIABILITY IS BASED ON CONTRACT, TORT, STRICT LIABILITY OR ANY OTHER THEORY.
11. Miscellaneous. If these terms are issued in connection with a government contract, they shall be deemed to include those federal acquisition
regulations that are required by law to be Included. These terms, together with any quotation, purchase order or acknowledgement issued or signed by the
Seller, comprise the complete and exclusive statement of the agreement between the parties (the "Agreement") and supersede any terms contained In
Buyer's documents, unless separately signed by Seller. No part of the Agreement may be changed or cancelled except by a written document signed by
Seller and Buyer. No course of dealing or performance, usage of trade or failure to enforce any term shall be used to modify the Agreement. If any of
these terms Is unenforceable, such term shall be limited only to the extent necessary to make It enforceable, and all other terms shall remain In full force
and effect. Buyer may not assign or permit any other transfer of the Agreement without Seller's prior written consent. The Agreement shall be governed by
the laws of the State of Delaware without regard to its conflict of laws provisions.
QUALITY FLOW SYSTEMS, INC.
800 6th street North West
New Prague, MN 56071
Office: (952) 758-9445
Fax: (952) 758-9661
August 20, 2007
To: Mr. Kelley Janes
City of Chanhassen
Re: Lift Station #3
Item Qtv. Descriotion
A. 1 Custom Powerpack Express in a free standing double door NEMA 3R enclosure
fabricated of galvanized steel and painted Forest Green. The enclosure will have a 3- !
point padlockable latch, skirted floor stand and inner doors. The equipment will control
the operation of two 30 HP submersible pumps, in a pump-down mode, in accordance
with the level of the wet well as monitored by a submersible level transducer and backup
float switches.
To Include: I
Incoming Service Information
Volts: 480 Phase: 3 Wire: 4 Hertz: 60
Pump Motor Information
HP: 30 FLA: approx 40 # of Pumps: 2 Pump Type: Submersible
GENERAL CONTROL PANEL REQUIREMENTS
1 UL 913
1 SERVICE ENTRANCE LABEL
CONTROL PANEL ENCLOSURE
1 LOW PROFILE
1 NEMA 3R
ENCLOSURE MATERIAL
1 STEEL
ENCLOSURE MODIFICATIONS
1 DEAD FRONT
1 LATCH (3-PT)
1 LEGS (12")
1 SKIRTS
1 PAINTED FOREST GREEN
1 CONDENSATION HEATER I THERMOSTAT
CIRCUIT BREAKERS
1 MAIN (200A thermal-mag w/auxiliary contact)
2 MOTOR
3 Q FRAME (CONTROL, ENGINE HEATER, BATTERY CHARGER)
1 RECEPTACLE (GFI)
LIGHTNING I SURGE ARRESTORS
2 PHASE MONITOR
1 LIGHTNING ARRESTOR
MOTOR STARTERS
2 SOLID STATE (Reduced Voltage Soft Start) (Motortronics, Model VMX)
MAIN CONTROLLER
1 0152 O-XX FT.
BACK.UP CONTROLLER
1 CBH
NEMA 4X INDICATOR LIGHT TYPE
2 120 VAC TRANSFORMER TYPE PRESS TO TEST LIGHTS
INDICATOR LIGHT FUNCTION.
2 PUMP RUN
NEMA 4X SELECTOR SWITCHES
2 3 POSITION SELECTOR SWITCH
SELECTOR SWITCH FUNCTION
2 PUMP HAND-OFF-AUTO
NEMA 4X PUSHBUTTONS
Item Q!'G Descriotion
1 MOMENTARY
PUSHBUTTON FUNCTION
1 ALARM SILENCE
RUNNING TIME METERS
2 PUMP RUN
1 SIMULTANEOUS PUMP RUN
OVERTEMP 1 SEAL FAIL
2 MINI CAS (MOUNT & WIRE MINI-CAS liON INNER DOOR)
ALARM DIALERS
1 ALARM HORN
1 ALARM LIGHT
MAIN TRANSDUCER
1 A1000GSCL SUBMERSIBLE LEVEL TRANSDUCER wI 60 ft. cable
1 A1000 CABLE SUSPENSION KIT wI 40 ft. cable
1 IS1-3 INTRINSIC SAFETY BARRIER 1-5 VDC
BACK-UP TRANSDUCER
3 LS FLOAT (SUSPENDED TYPE)
1 IS6 INTRINSIC SAFETY BARRIER
MISCELLANEOUS
1 300 AMP - AUTOMATIC TRANSFER SWITCH (ASCO SERIES 300)
1 TRANSFORMER 480/120 VOLT 3 KV A W/PRI & SEC FUSING
Total sell price for Item A is $26.248 neti excluding all taxes and commissions.
~
. 2~ <7~tI,IZ
If you have questions, please give me a call.
Thank you,
@:wa~1