July 28, 2004
William Tippmann
9549 Montgomery Rd.
Suite 300
Cincinnati, OR 45242
Dennis O'Beime
25200 Telegraph Rd.
Southfield, MI 48034
Bob Besuden
CVS/Pharmacy Inc.
28003 Eight Mile Rd.
Livonia, MI 48152
Re:
Mechanical Plan review for:
CVS Pharmacy
7765 Galpin Blvd.
Chanhasser1~MN 55317
Gentlemen:
As a supplementto theþuilciing plan review letter d~t@rl;rtiIY~7, 2?04; this letter
contains comme:nts'felªt~d.tgthe ph1Jl1þing and m~º:J:"ta,piç~:!ls¥$t~m§~
Mechanical & e;as
1) Submit applicatiòiïf()í"PëJ?111it.~ÇJ~Ö~ ..... ......... ............ .........
2) Sheet M -l.l.Pròvide combustioi1<iit~Qttl1~ mV,tl1§ªt~:t ill $lï~,t~º¢ryí):').~ÇI.t~ªi
Submit revised plans. UMC 601(a).
3) Sheet M-1.2. Smoke detectors are required in the supplies a,nd ret.ums ()f an
RTU's. Submit revised plans. UMC 1009(a).
4) Sheet M-1.3. The plans show low pressure gas and a condensate piping
system from the RTU's. Both of these items comply with code, but are not
. typically installed. Revised plans are required if any changes are done to
approved plans. Informational only.
Plumbine;
5) Sheet P 1.1. The plans show the sanitary service to the building in three
separate areas. This doescÒmply with the'MPC, but is a very unusual
installation. Revised plans arerequirt;d if any changes are done to approved
plans. Informational only.
The City of Chanhassen · A growing community with clean lakes, quality schools, a charming downtown, thriving businesses, winding trails, and beautiful parks. A great place to live, work, and play.
June 28, 2004
Page 2
6) Sheet P-l.l & P-l.2. RPBP are only allowed on non-potable systems.
Submit revised plans. MPC 4715.2020.
7) Sheet P-l.l & P-l.2. It appears some fixtures are flat vented which is not
permitted by the MPC. Submit revised plans. I\.1PC 4715.2540
8) Sheet P-1.2. The plans do not show a water feed to the film processor.
Submit revised plans. MPC 4715.2020.
9) Sheet P-1.3. Verify all piping on the water purification system complies with
the MPC. MPC 4715.0410
Other issues may arise which will also require your attention. Changes made by
issuing revised plan sheets must have the revision clouded and the revision
date shown. Submit three copies of only those sheets being revised, one with
the original signature of the design professional. Changes to the plans by
addenda, bulletin or similar methods must also be submitted in the same fashion.
In the event that plumbing and/or mechanical contractors wish to submit alternate
plans, such plans must be signed by a Minnesota licensed mechanical engineer and
approved by the "designated design professional" (James R. Fox) named on "Sheet
CS, Team Members" of the CVS Pharmacy plans.
Please call ifyouþave any questions, 952-227-1196.
erritt Mohn
Building Inspector
cc: Steve Torell, Building Official