Septic Field Sizing CalculationsOctober 18tH, 2020 Dale Denn Homestead Septic 1108 Goldenrod Lane Shakopee, MN 55379 MPCA License # 583 To: John Wicka Subject: Septic Field Sizing Calculations 1601 Lake Lucy Road Excelsior, MN 55331 Dear John, Here are the Septic System Drainfield sizing calculations based on a total number of 7 bedrooms for two residential use units on the property. Preliminary Disclosure: 1. No soil borings have been done to validate the type, use, nor extent of suitable soils for a drainfield. 2. No percolation test have been conducted. 3. The depth to a seasonally saturated soil water level is based upon worst case soils scenario of just having the minimum of 12 inches of suitable soil above a restricting layer. 4. Septic sizing criteria is based on the soil characteristics of a clay loam soil designing for a Mound on an estimated 6 percent slope. 5. No preliminary staking of rock and sand beds to reflect the overall footprint of the system has been done. 6. Slope direction, length, and contours have not been established. 7. Essentially, the attached septic sizing information is not a design and the design forms utilized are just to generate the overall square footage needed to fit a primary and a secondary septic system on this property. Sizing requirements per estimated septic calculations: A. Primary Mound for 7 bedrooms is 45 x 122'. Or about 5500 square feet. 1. This would require a same elevation contour length of 122'. B. A matching Alternate site would be the same: 5500 square feet. 1. This would also require a same elevation contour length of 122'. C. There would be options to break the total system in half as far as placement and siting goes to adjust to natural features of the landscape. But the overall square footage requirement would remain the same or actually require more area. D. Or one 5 bedroom system could be designed and placed for the home and one 2 bedroom system designed and placed for the guest home. Square footage would again be about the same or end up a bit larger. Exhibit 1. This area depicts the total area available for both the Primary and the Secondary Septic Sites for this property. This area is determined and plotted by 'others' and not Homestead Septic. No field or soil verifications have been made in this proposed area by Homestead Septic. The proposed septic area is 12984 square feet. Septic area required from estimated calculations total about 11,000.00 square feet. These Septic Calculations and estimate Septic Sizing requirements have been accomplished by Dale Den n/Homestead Septic. MPCA Licensed #583. Dale Denn r / JJ/FF �FFF %qj� r�rJ lw1/: wwrJ j 'sixi�iwr �wwwb %isi.%iwr.._ '�v�x'• r �wsr.riaaiiwrr... errriir�irxr _. �+is,cw�si� rss � ws srrr . a- r w v swiiiriirrirrrrw�xr wwxrrrrrr+-,-- rsr r rr�rrrrrrrsrwww�w ^- rr..i�rrrir r xrw,rrriw� +z% rrrrrwrrr--^ _wwrr r� as Ps• — - r / JJ/FF �FFF %qj� r�rJ lw1/: wwrJ j 'sixi�iwr �wwwb %isi.%iwr.._ '�v�x'• r �wsr.riaaiiwrr... errriir�irxr _. �+is,cw�si� rss � ws srrr . a- r w v swiiiriirrirrrrw�xr wwxrrrrrr+-,-- rsr r rr�rrrrrrrsrwww�w ^- rr..i�rrrir r xrw,rrriw� +z% rrrrrwrrr--^ _wwrr r� �r—operty Card Parcel ID Number 254070200 Taxpayer Information Taxpayer Name JOHN D WICKA ANNE WICKA Mailing Address 2547 BRIDLE CREEK TRL CHANHASSEN, MN 55317 - Property Address Address 1601 LAKE LUCY RD EXCELSIOR, MN 55331 Parcel Information Uses Res V Land GIS Acres 9.02 Net Acres Deeded Acres 0.45 Plat Lot Block Tax Description Building Information Building Style Above Grade Bedrooms Homestead N Finished Sq Ft Year Built Garage Miscellaneous Information School District Watershed District 0276 WS 064 RILEY PURL BLUFF Homestead N Green Acres Ag Preserve N Assessor Information Estimated Market Value 2018 Values (Payable 2019) 2019 Values (Payable 2020) Last Sale Land $1,039,200.00 Date of Sale 7110/2018 Building $23,800.00 Sale Value $1,150,000.00 Total $1,063,000.00 I he data provided Ins ith is for refomneo purposes only, This data ie not suitable for 1o9al, ongineering, survoyinq ar other cimiiar pure c— Carer Courcy does roi guarantee the accuracy of the information contained herein. This data is furnished on an 'as is' basis and Carver County makes no representations or warranties, either expressed or implied, for the merchantability or fitness of the information provided for any purpose, This disclaimer is provided pursuant to Minnesota Statutes §466.03 and the user of the data provided herein acknowledges that Carver County shall not be liable for any damages, and by using this data in any way expressly waives all claims, and agrees to defend, indemnify, and hold harmless Carver County, its officials, officers, agents, employees, etc. from any and all claims brought by anyone who uses the information provided for herein, its employees or agents, or third parties which arise out of user's access_ By acceptance of this data, the user agrees not to transmit this data or provide access to it or any part of it to another party unless the user includes with the data a copy of this disclaimer. Monday, February 17, 2020 Carver County, MN . �� iw � rw�i%ir.:rcrsrwi ri _-+irii«ir� �wwrr /iters w -vrri 1 � 1 1 I r a I I I , _ 1 , I , , rar:r lziwws �� I1 •or �� wr �:►,iarw �wiwwa swrrr. �irr w r F tirri� �.rrwrr rar:r lziwws �� viifSE R� 1 1 1 1 I I l i i i d 1 1 1 I 1 r F �ff 1 r 1 �� viifSE R� 1 1 1 1 I I l i i i d 1 1 1 I 1 ♦\ i 1 1 1 - 1 ♦ \ 1 1 1 \ 4 I 1 4 1 \ \ 1 1 \5 V 1 5 \ 4 \ � 1 �� viifSE R� a a z MEW I n � �Yr �' �K0.La3 {Ci CGdli; ----------------------J—_ _— •an_.;_— axLotS) /f "o,�sRTz.A LA& Preliminary SwAGe MINNESOTA POLLUTION TitEATW1C0 Evaluation Worksheet M CONTROL AGENCY ftCSGRh9 "�. 1. Contact Information v 04.01.2020 Property Owner/ Client: John Wicka Date Completed: 10/18/2020 Site Address: 1601 Lake Lucy Road, Excelsior, MN 55331 Project ID: Email: John.Wicka@gmail.com Phone: 612-805-6250 Mailing Address: 2547 Bridle Creek Trail, Chanhassen, MN 55317 Legal Description: Parcel ID: 254070200 SEC: TWP: E= RNG: 2. Flow and General System Information A. Client -Provided information Project Type: El New Construction ❑ Replacement ❑ Expansion ❑ Repair Project Use: El Residential ❑ Other Establishment: Residential use: # Bedrooms: Dwelling Sq.ft.: Unfinished Sq. Ft.: # Adults: # Children: # Teenagers: In-home business (YIN): No If yes, describe: El Garbage Disposal/Grinder El Dishwasher 0 Hot Tub* Water -using devices: M Sewage pump in basement El Water Softener* 0 Sump Pump* (check all that apply) E41 Large Bathtub X40 gallons Cl Iron Filter* ❑ Self -Cleaning Humidifier* 0 Clothes Washing Machine I] High Eff. Furnace* ❑ Other: * Clear water source - should not go into system Additionat current or future uses: done Anticipated Anticipated non-domestic waste: None The above is complete Ft accurate: Client signature Ft date B. Designer -determined flow Information Attach additional information as necessary. Design Flow: 1050 GPD Anticipated Waste Type: Residential BOD: X170 mg/L TSS X60 mg/L Oil Et Grease X25 mg/L_ 3. Preliminary Site Information A. Water Supply Wells Well Depth Casing Confining STA # Description Mn. ID# (ft.) Depth (ft.) Layer Setback Source 1 >50 50 50' 2 3 4 Additional Well Information: oM��* Preliminary SfWAG& MINNESOTA POLLUTION ,RC,Ar Evaluation Worksheet m CONTROL AGENCY Site within 200' of noncommunity transient well (Y/N) No Yes, source: Site within a drinking water supply management area (Y/N) No Yes, source: Site in Well Head Protection inner wellhead management zone (Y/N) Na Yes, source: Buried water supply pipes within 50 ft of proposed system (Y/N) No B. Site located in a shoreland district/area? Yes Yes, name: Lucy Elevation of ordinary high water level: ft Source: Classification: Lake - General Development Tank Setback: ft. STA Setbk: ft. C. Site located in a floodplain? No Yes, Type(s): NIA Floodplain designation/ elevation (10 Year): NIA ft Source: N/A Floodplain designation /elevation (100 Year): NIA ft Source: NIA D. Property Line Id / Source: ❑ owner 2 Survey ❑ County GIS ❑ Plat Map ❑ Other: E. ID distance of relevant setbacks on map: 0 water l] Easements ❑ Weil(s) R Building(s) El Property lines 0 OHWL ❑ Other: 4, Preliminary Soil Profile Information From Web Soil Survey (attach map & description) Map Units: Lester/Killkenny Loams Slope Mange: 2 12% % List landforms: Upland Summit/River Terrace interluve Landform position (s): Back/Sideslope Parent materials: Till/Lucustrine Depth to Bedrock/ Restrictive Feature:in Depth to Watertable:in Septic Tank Absorption Field- At -grade: Map Unit Ratings Septic Tank Absorption Field- Mound: Septic Tank Absorption Field- Trench: 5. Local Government Unit Information Name of LGU: City of Chanhassen LGU Contact: Eric - LGU-specific setbacks: Same as 7080 but have Bluff Ordinance LGU-specific design requirements: Same as 7080 but have Bluff Ordinance LGU-specific installation requirements: Same as 7080 but have Bluff Ordinance Notes: ,, Field ov�3�g 5cwarf MINNESOTA POLLUTION LATfkNs„ Evaluation Worksheet CONTROL AGENCY 1. Project Information v 04.01.2020 Property Owner/Client: John Wicka Project ID: Site Address: 1601 Lake Lucy Road, Excelsior, MN 55331 Date Completed: 2. Utility and Structure Information Utility Locations Identified ❑ Gopher State One Call # ❑ Any Private Utilities: Locate and Verify (see Site Evaluation map) 0 Existing Buildings [Z Improvements Q Easements Q Setbacks 3. Site Information Vegetation type(s): Forest Landscape position: Back/ Side Slope Percent slope: 6 % Slope shape: Linear, Linear Slope direction: south Describe the flooding or run-on potential of site: Describe the need for Type III or Type IV system: Note: Proposed soil treatment area protected? (YIN): Yes If yes, describe: Location 4. General Soils Information Filled, Compacted, Disturbed areas (YIN): If yes, describe: Soil observations were conducted in the proposed system location (YIN): A soil observation in the most Limiting area of the proposed system (Y/N): Number of soil observations: Soil observation logs attached (YIN): Percolation tests performed a attached (YIN): 5. Phase I. Reporting Information Depth Elevation Limiting Condition*: 12 in ft `Most Restrictive Depth Identified from List Below Periodically saturated soil: 12 in ft Soil Texture: Standing water: in ft Percolation Rate: min/inch Bedrock: in ft Soil Hyd Loading Rate: 1.2 Igpd/ft2 Benchmark Elevation: 100.0 ft Elevations and Benchmark on map? (Y/N): Benchmark Elevation Location: Differences between soil survey and field evaluation: Site evaluation issues / comments: Anticipated construction issues: E:I PCSST£ SFWAI Pe TREA'€PIEA[ r V�, GRA�:1 y� MINNESOTA POLLUTION Design Summary Page CONTROL AGENCY 1. PROJECT INFORMATION v 04.01.2020 Property Owner/Client: John Wicka Project ID: Site Address:1601 Lake Lucy Road, Excelsior, MN 55331 Date: 10/18/20 Email Address: John.Wicka'@gmait.com Phone: 612-805-6.250 2. DESIGN FLOW Ft WASTE STRENGTH Attach data / estimate basis for Other Establishments Design Flow: 1050 GPD Anticipated Waste Type: Residential BOD: <170 mg/L TSS: <60 mg/L Oil Ft Grease: <25 mg/L Treatment Level: E=Select Treatment Level C for residential septic tank effluent 3. HOLDING TANK SIZING Minimum Capacity: Residential =400 gal/bedroom, Other Establishment = Design Flow x 5.0, Minimum size 1000 gatlons Code Minimum Holding Tank Capacity: Gallons in Tanks or Compartments Recommended Holding Tank. Capacity: Gallons in Tanks or Compartments Type of High Level Alarm: {Set C 75% tank capacity) Comments: 4. SEPTIC TANS( SIZING ..............................................................................................._...............................__..........._...._...._.........._.___....._............ .......... gal dwellings: A.Re _. ,.__..._,..._..__.....___.__...._._,.....,..._..._.............,..�......: Number Number of Bedrooms (Residential): Code Minimum Septic Tank Capacity: 3000 Gallons in Tanks or Compartments Recommended Septic Tank Capacity: 3000 Gallons in Tanks or Compartments Effluent Screen & Alarm (YIN): Optional Model/Type: ........._........................._.......................... ................. ....... ................._...._._..._......................... ............. __......._....__..... _................_... B. Other Establishments. ................................... ...... ..W .......... ................... ....... ...... ...... .......m.....,..._m___.....�__.._�...__....., Waste received by: 0 GPD x =Days Hyd. Retention Time Code Minimum Septic Tank Capacity:Gallons In Tanks or Compartments Recommended Septic Tank Capacity:Gallons In Tanks or Compartments Effluent Screen Ft Alarm (YIN): Model/Type: 5. PUMP TANK SIZING Pump Tank 1 Capacity (Minimum):Gal Pump Tank 2 Capacity (Minimum): Gal Pump Tank 1 Capacity (Recommended): Gal Pump Tank 2 Capacity (Recommended): Gal Pump 1 GPM Total Headft = Pump 2GPM Total Headft Supply Pipe Dia.in Dose Vol:gat Supply Pipe Dia. Dose Vol.:Gat SEWAGE TFeEnYS tr: P GGRw MINNESOTA POLLUTION Design Summary Page Im CONTROL AGENCY G. SYSTEM AND DISTRIBUTION TYPE Project ID: Soil Treatment Type: Mound Distribution Type: Pressure Distribution -Level Elevation Benchmark: 100 ft Benchmark Location: MPCA System Type: Type I Distribution Media: Type III/IV Detai Is: 7. SITE EVALUATION SUMMARY: . ......... .... ..... . ................................................ . ................ .... ......... ... ..... ........ ............... . .... ... .... .... .... .. .... ............................ . .. ......... ....... . ... I ........... .. .. . .......... ......... .. ..... . .......... . ... . ......... ........ ........ .......... ....... . . ......... Describe Limiting Condition: F Redoximorphic Features/ Saturated Soils Layers with >35% Rock Fragments? (yes/no)= If yes, describe below: % rock and layer thickness, amount of soil credit and any additional information for addressing the rock fragments in this design. 'Note: Depth Depth Elevation of Limiting Condition Limiting Condition: 12 inches1.0 ft ft Minimum Req'd Separation: 3b inches 3.0 ft Elevation Critical for system compliance Code Max System Depth: Mound inches E9 ft ft is the maximimum depth to the bottom of the distribution media for required separation. NeRative Depth (ft) means it must be a mound .......... .. ..... .. .. .. ... .. .......... .............. ....... . ..... .. ..... .. . ......... ....... ...... - ....... .... --- .. .. ... .. . ..... ..... ..... Soil Texture: F Clay Loam I Soil Hyd. Loading Rate: 0.45 GPD/ft' Percolation Rate: MPI Contour Loading Rate: 12 Note: F Measured Land Slope: 6.Q % Note: Comments: I 8. SOIL TREATMENT AREA DESIGN SUMMARY Trench: Dispersal Area ft 2 Sidewalk Depth in Trench Width ft Total Lineal Feet ft No. of Trenches Code Max. Trench Depth in Contour Loading Rate ft Length ft Designed Trench Depth in Bed: Dispersal Area ft2 Sidewall Depth in Maximum Bed Depth in Bed Width ft Bed Length ft Designed Bed Depth in Mound: Dispersal Area 875.0 ft2 Bed Length 87.5 ft Bed Width 10.Q ft Absorption Width 26.Q ft Clean Sand Lift 2.0 ft Berm Width (0-1%) ft Upslope Berm Width 12.3 ft Downslope Berm z3.1 ft Endslope Berm Width 17.5 ft Total System Length 122.7 ft System Width 45.4 ft Contour Loading Rate 12.0 gal/ft Project ID: 11r.h irt+rt F9..tart. Omsm SFWZG TREATMENT MINNESOTA POLLUTION Design Summary Page CONTROL AGENCY At -Grade: - - Bed Widthft Bed Lengthft Finished Heightft Contour Loading Rategal/ft Upslope Bermft Downslope Bermft Endslape Bermft System Lengthft System Width ft Level it Equal Pressure Distribution No. of Laterals Perforation Spacingft Perforation Diameterin Lateral Diameter 0.00 in Min Dose Volume gat Max Dose Volume 263 gal Non -Level Lateral 1 Lateral 2 Lateral 3 Lateral 4 Lateral 5 Lateral 6 and Unequal Pressure Distribution Perf Size (in) Spacing {ft} Spacing (in} Minimum Dose Volume gal Maximum Dose Volume gal Elevation Pipe Size Pipe (ft} I hereby certify that I have completed this work in accordance with all applicable ordinances, rules and laws. E: Dale Denn 583 10/18/2020 (Designer) {in) Volume (gal/ft) Pipe Length {#fi) Perf Size (in) Spacing {ft} Spacing (in} 9. Additional Info for At -Risk, FISW or Type IV Design A. Starting BOD Concentration = Design Flow X Starting BOD (mg/L) X 8.35 : 1,000,000 �gpd X �mg/L X 8.35: 1,000,00( = lbs. BOD/day B. Target BOD Concentration = Design Flow X Target BOD (mg/L) X 8.35 _ 1,000,000 �gpd X �mg/L X 8.35 : 1,000,00( _ lbs. BOD/day Lbs. BOD To Be Removed: PreTreatment Technology: `Must Meet or Exceed Target Disinfection Technology: Required for Levels A Et B C. Organic Loading to Soil Treatment Area: =mg/L X =gpd x 8.35 1,000,000 = �ftz = lbs./day/W 10. Comments/Special Design Considerations: (Signature) (License #) (Date) inutnxn a fG•�vuu CTnsa-ra SEY`�AGE TREAvviEur PROGRAM y__ 1h�...7- Mound Design 1 Worksheet MINNESOTA POLLUTION >A% Slope M-11 CONTROL ,AGENCY 1. SYSTEM SIZING: Project ID: v 04.01.2020 A. Design Flow: B. Soil Loading Rate: C. Depth to Limiting Condition D. Percent Land Slope: E. Design Media Loading Rate: F. Mound Absorption Ratio: 1050 IGPD GPD/ft 2 1.0 ft 6.0 % 1.2 GPD/ft2 2.60 Tabie I MOUND CONTOUR LOADING RATES: Measured Treatment Levei C TOxtury - darivvd A, A-2, B, Absorption Area Loafts Nbuod Rate Awn Ir1p �7 Ratio Porc Rata OR matmd absorption rat 01 W5 1.2 1 1.6 1 s 60nipi OR 1.0. 1.3. 2,0, 2.4. 2.6 rf6 61-120 nlpi 5.0 120 mpi` -5.0' DISPERSAL MEDIA SIZING TABLE IXa 0.45 LOADING RATES FOR DETERMINING BOTTOM ABSORPTION AREA AND ABSORPTION RATIOS USING PERCOLATION TESTS Percolation Rate (MPI) Treatment Levei C Treatment Level A, A-2, B, Absorption Area Loafts Nbuod Rate Awn Ir1p �7 Ratio ArAbsorption s Rate (f Rate) Mound Absorption Ratio 01 W5 1.2 1 1.6 1 0 1 to 5 (fine santl and ipanr fin¢ sa 0.6 2 1 1.6 16 to 30 0.6 2 0.7$ 2 31 to 45 0-5 2A 0.7$ 2 46 10 60 0.45 2.6 0.6 2.fi 61 to 120 - 6 0.3 5.3 120 *Systems with these values are not Type I systems. Contour Loading Rate (linear loading rate) is a recommended value. A. Calculate Dispersal Bed Area: Design Flow _ Design Media Loading Rate 1050 GPD 1.2 GPD/ft2 = 875 ft2 If a larger dispersal media area is desired, enter size:ft B. Enter Dispersal Bed Width: 10.0 ft Can not exceed 10 feet C. Calculate Contour Loading Rate- Bed Width X Design Media Loading Rate i0 ft 7. X 1.2 GPD/ft2 = 12.0 gal/ft Can not exceed Table 1 D. Calculate Minimum Dispersal Bed Length: Dispersal Bed Area : Bed Width 875 ft2 10.0 ft = 87.5 ft 13. ABSORPTION AREA SIZING I A. Calculate Absorption Width: Bed Width X Mound Absorption Ratio 10.0 ft X Z.6 - 2b.0 ft B. For slopes >1%, the Absorption Width is measured downhill from the upslope edge of the Bed. Calculate Downslope Absorption Width: Absorption Width - Bed Width 26.0 ft - 10.0 ft = 15.0 ft 14. DISTRIBUTION MEDIA: ROCK Project ID: I A. Rock Depth Below Distribution Pipe 6in 0.50 ft 15. DISTRIBUTION MEDIA: REGISTERED TREATMENT PRODUCTS: CHAMBERS AND EZFLOW A. Enter Dispersal Media: B. Enter the Component: Length: ft Width: ft Depth: ft C, Number of Components per Row = Bed Length divided by Component Length (Round up) ft : ft = components/row Check registered product D. Actual Bed Length = Number of Components/row X Component Length: information for specific components X ft = application details and E. Number of Rows = Bed Width divided by Component Width (Round up) design ft : ft = L� rows Adjust width so this is a whole number. F. Total Number of Components = Number of Components per Row X Number of Rows X _components 16. MOUND SIZING A. Clean Sand Lift: Required Separation - Depth to Limiting Condition = Clean Sand Lift (1 ft minimum) 3.0 ft - 1.0 ft = 2.0 ft Design Sand Lift (optional): ft B. Upslope Height: Clean Sand Lift + Depth of Media +Depth to Cover Pipe+ Depth of Cover (1 ft) 2.0 ft + 0.50 ft + 0.3 ft + 1.0 fit = 3.8 ft Land Slope %0 1 2 3 4 5 6 7 8 9 10 11 12 Upslope Berm Ratio 14414.00 3.00 2.91 2.83 2.75 2.6$ 2.61 2.54 2.48 2.42 2.36 2.31 1 2.26 2.21 3.85 3.70 3.57 3.45 3.33 3.23 3.1.2 3.03 2.94 12.86 2.78 12.70 C. Select Upslope Berm Multiplier (based on land slope): 3.23 D. Calculate Upslope Berm Width: Multiplier X Upslope Mound Height 3.23 ft X 3.8 ft = 12.3 ft E. Calculate Drop in Elevation Under Bed: Bed Width X Land Slope _ 100 = Drop (ft) 10.0 ft X b.0 % : 100 = 0.60 ft F. Calculate Downslope Mound Height: Upslope Height + Drop in Elevation 3.8 1 ft + 0.60 I ft =1 4.4 Land Slope % 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 1 10 1 11 1 12 Downslope 3:1 3.00 3.09 3.19 3.30 3.41 3.53 13,66 1 3.80 1 3.95 1 4.11 4-2-9-F4.48 1 4.69 Berm Ratio 14:114.00 14.17 1435 14.54 14.76 1 5.00 1 5.26 15.56 1 5.88 1 6.25 1 6.67 1 7.14 1 7.69 G. Select Downslope Berm Multiplier (based on land slope): 5.26 H. Calculate Downslope Berm Width: Downslope Multiplier X Downslope Height 5.26 x 4.4 ft = 23.1 ft I. Calculate Minimum Berm to Cover Absorption Area: Downslope Absorption Width + 4 feet 16.0 ft + ft = 20.0 ft J. Design Downslope Berm = greater of 4H and 41: 23.1 ft K. Select Endslope Berm Multiplier: 4.00 (usually 3.0 or 4.0) L. Calculate Endslope Berm X Downslope Mound Height = Endslope Berm Width 4.00 ft X 4.4 ft = 17.6 ft M. Calculate Mound Width: Upslope Berm Width + Bed Width + Downslope Berm Width 12.3 ft + 10.0 ft + 23.1 ft = 45.4 ft N. Calculate Mound Length: Endslope Berm Width + Bed Length + Endslope Berm Width 17.6 J ft + 87.5 ft + 17.6 ft = 122.7 ft 7. MOULD DIMENSIONS Project ID: Upslope i Ends�lope Dispersal Bed: 1�.6 10.0 X $7.� 23.1 Downslope 4' inspection piAe r..— IS- cover On top 12.3 i.0 Clears sand iaft Clean Sand Comments: 122.7 2b.0 I 23.1 12` cover a -.t sides t5' tosoitl